35kv cable-linking cable outdoor, indoor terminal

heat shrinkable mid die-Voltage product is suitable for the end deaing and intermediate link of 6RV-15KV cross-linking cable.The product are classified single core,three cores.The distande is 650mm for the indoor terminal installaaticr it has 800mm,1000mm accrdance with the demands of user.The distance is 650mm for outdoor terminal installation.It ha<800mm,1000mm accordance with the demands of user.

Product specificatio

Name Type Section

10KV indoor cross-link three-cores terminals

10KV outdoor cross-link three-cores terminals

NSY-10/3.1 25-50
NSY-10/3.2 70-120
NSY-10/3.3 150-240
NSY-10/3.4 300-500
WSY-10/3.1 25-50
WSY-10/3.2 70-120
WSY-10/3.3 150-240
WSY-10/3.4 300-500
10KV indoor oil-dipped three-cores terminals NSZ-10/3.1 25-50
NSZ-10/3.2 70-120
NSZ-10/3.3 150-240
10KV outdoor oil-dipped three-cores terminals WSZ-10/3.1 25-50
WSZ-10/3.2 70-120
WSZ-10/3.3 150-240

Product techniacal index

Name Type Section

10KV outdoor cross-link three-cores terminals

WSY-10/3.1 25-50
WSY-10/3.2 70-120
WSY-10/3.3 150-240
WSY-10/3.4 300-500
10KV indoor oil-dipped three-cores terminals NSZ-10/3.1 25-50
NSZ-10/3.2 70-120
NSZ-10/3.3 150-240

The designed of single core cable and special section in accordance with demands of user
Product techniacal index

ltem Test item Standard Result Note
10kV outdoor indoor terminal and intermiediate joint 1 main frequency withstand voltge 4KV 1min2 non-flashover,non-puncture 4KV 1minnon-flashover,non-puncture Pass
2 partial discharge test 13KV ≤ 20pC 13KV 8pC Pass
3 conduct load cycle testing for 3 periods Heating for 5 hours and cooling for 3 hours,the temperature of conductor is 95℃ during heating process. Heating for 5 hours and cooling for 3 hours,the temperature of conductor is 95℃ during heating process Pass
4 parial discharge test 13KV ≤ 20pC 13KV 10pC Pass
impulse voltage test:one time for 1.2/50us positive pole and negative pole respectively 105KV one time flashover of 105Kv positive pole and negative pole respectively is allowed,but this is not numbered as total test times. 105KV non-flashiover,non-puncture Pass
6 DC voltage test negative polarity 15KV/15min non-flashiover,non-puncture 52KV/15min non-flashiover,non-puncture Pass
7 4h same frequency voltage test 35KV 4h min non-flashiover,non-puncture 34KV/4h non-flashiover,non-puncture Pass