| ltem | 
              Test item  | 
              Standard | 
              Result | 
              Note | 
            
            
              | 35kV outdoor indoor terminal  | 
              1 main frequency withstand voltge | 
              105KV non-flashover,non-puncture | 
              105 1minnon-flashover,non-puncture | 
              Pass | 
            
            
              | 2 partial discharge test  | 
              39KV ≤ 10pC  | 
              13KV ≤ 10pC  | 
              Pass | 
            
            
              | 3 conduct load cycle testing for 3 periods  | 
              Heating for 5 hours and cooling for 3 hours,the temperature of conductor is 75 ℃ during heating process. | 
              same as the left | 
              Pass | 
            
            
              | 4 parial discharge test  | 
              39KV ≤ 10pC  | 
              39KV 110pC  | 
              Pass | 
            
            
              | impulse voltage test:one time for 1.2/50us positive pole and negative pole respectively  | 
              250KV non-flashover,non-puncture | 
              250KV ± time non-flashiover,non-puncture | 
              Pass | 
            
            
              | 6 DC voltage test negative polarity | 
              156KV non-flashiover,non-puncture | 
              156KV/15min non-flashiover,non-puncture | 
              Pass | 
            
            
              | 7 4h same frequency voltage test | 
              104KV 4h min non-flashiover,non-puncture | 
              34KV/4h non-flashiover,non-puncture | 
              Pass |