HR6 series Fuse Type Isolating Switch

Application
This series can be used in the circuit of rated voltage up to 690V,AC 50Hz(or 60Hz),and conventional free air heating current up to 630A. It is applicable for distribution circuit of high short-circuit current and motor circuit, serving for power switch, isolating switch,emergergency switch as well as circuit protector.Generally,it can not be used for directly switching of single motor and is for use indoors. This switch can be mounted in the cabinet as well as on the panel of cabinet, providing new low-voltage electruc element for complete set of electric control equipment.

Model and Definition


Normaol Working Conditions
1.The ambient air temperature shall exceed +40¡æ, The average value shall not exceed +35¡æ within 24 hours,The lower-limitof ambient air temperature is -5¡æ.
2.Generally, height above sea level shall not exceed 2000m.For higher height above sea level.consult with manufacturer.
3.When at max.temperature of +40¡æ,relative air humidity shall not exceed 50%. Higher relative humidity such as 90% at the temperature of 20¡æ.if allowed under lower temperature. Special measuer shall be taken against occasional condensation caused by temp.change.
4.Pollution grade:pollution grade of ambient environment of switch is 3.
5.Switch shall be vertically installed in a place without obvious vibration or impact vibration.


Structural Features
This switch is composed of two parts: base and switch cover.The base is mounted with contct and arc-extinguishing system. The fuse body is mounted on the switch cover, directly serving for moving contact blade. The base and switch cover are made of plastic through pressing.Therefore, it is of small volume, light weight and beautiful outline, etc.

Main Technical Data
Rated working
voltage(v)
Rated working
current(a)
Using
category
Rated making and breaking capabitlity
Rated fuse short-circuit current(KA)
Making
Breaking
Operation
cycle index
Current
effective value
COS¦Õ
I/Ie
U/Ue
COS¦Õ
I/Ie
U/Ue
COS¦Õ
380
160
200
400
630
AC-21B
1.5
1.05
0.95
1.5
1.05
0.95
5 order
100
0.2
AC-22B
3
0.65
3
0.65
160
200
400
630
AC-23B
10
0.45
8
0.45
0.35
0.35
3 order
660
160
200
315
425
AC-21B
1.5
1.05
0.95
1.5
1.05
0.95
5 order
50
0.25
AC-22B
3
0.65
3
0.65
Rated working
voltage
Using
category
making
Breaking
I/Ie
U/Ue
COS¦Õ
I/Ie
U/Ue
COS¦Õ
380
AC-23
1
1
0.65
1
1
0.65
660
AC-22
1
1
0.8
1
1
0.8

Conventional free air heating currentof switch
Rated working voltage(A)
Rated working
current of switch(A)
Fuse size
Rated current of fuse body(A)
100
380
160
00
4,6,10,16,20,25,32,35
40,50,63,80,100,125,160
660
4,6,10,16,20,25,32,35
40,50,63,80,000
200
380
200
1
80,100,125,160,200,224
660
80,100,125,160,200,250
400
380
315
2
125,160,200,224,250,300,315,355,400
660
125,160,200,224,250,300,315
630
380
630
3
315,355,400,425,500,630
660
425
315,355,400,425
Note: When the switch is used switch is used in motor circuit,rated current of fuse body is allowed to be larger than rated working current of switch.
Outline and Installation Size
 
Rated current
Amax
Bmax
C
D
Emax
Fmax
G
H
I
¦µa
¦µb
106A
223.5
138
207
90
152
255
30¡À0.60
160
40
8-6.5
4-5.5
200A
296
200
286
156
183
355
52¡À0.70
195
60
8-8.5
4-5.5
400A
296
264
286
225
210
373
75¡À0.80
195
60
8-8.5
4-5.5
630A
293
264
286
225
210
373
75¡À0.80
195
60
8-8.5
4-5.5

Notice for Order

When ordering HR6 series fuse type isolating switch ,the user shall specify tne following
contents:Description,, model, conventional free air heating current,number of poles,whether with fuse body or inching switch,rated current of applicable fuse body(if not,assemble according to conventional free air heating current) and quantity of switches,etc.e.g.HR6-160/311 whith 10 fuse of 100A